SCC-T1-Tp2 - PT1000

Active temperature transmitter for large and accurate measuring range
The transmitter measures the temperature for a PT1000 platinum film element. The transmitter does not include the PT1000 sensor. An external PT1000 according to EN 60751 has to be connected for the transmitter to operate.
The microprocessor samples the temperature once per second. It calculates an averaging signal over a preset number of seconds and generates an output signal based on lower and upper signal range values. Standard range is
-40…400°C (-40…752°F) and 1 seconds average.
A version with a display is possible by ordering the integrated display accessory OPC-S.
Applications
- For indoor, outdoor, duct, immersion temperature measurement for heating, ventilation and air conditioning applications.
- Recording of minimum and maximum values for critical environments
- Supervision of critical temperatures
Features
- Precision temperature measurement for different ranges and accuracies
- Minimum and maximum value memory
- 0…10V, 0…20mA or 2…10V, 4…20mA measuring signals, selectable with jumpers
- Optional alternative signal ranges programmable
- Selectable averaging signal
- Optional LCD display (OPC-S) or external display (OPA-S)
- Status LED
Ordering
Item name | Item code | Definition |
SCC-T1-Tp2 | 40-300075 | Temperature transmitter without PT1000 sensing element. Temperature range: -40…400°C (-40…752°F) |
SCC-T1-Tp2-OP | 40-300076 | Temperature transmitter as above with display. Temperature range: -40…400°C (-40…752°F) |
Accessories

Temperature Sensors
Passive temperature sensors for a large variety of installation options and applications

OPC-S - Built-in Display
Operation and display for intelligent duct and outdoor transmitters

OPA-S - Remote Display
Operation and display for intelligent transmitters
Downloads
Operation Manual
Install Sheet
Application Notes
Certificates
Archive