SCC-T1-Tp2 - PT1000

#

Active temperature transmitter for large and accurate measuring range

The transmitter measures the temperature for a PT1000 platinum film element. The transmitter does not include the PT1000 sensor. An external PT1000 according to EN 60751 has to be connected for the transmitter to operate.

The microprocessor samples the temperature once per second. It calculates an averaging signal over a preset number of seconds and generates an output signal based on lower and upper signal range values. Standard range is
-40…400°C (-40…752°F) and 1 seconds average.

A version with a display is possible by ordering the integrated display accessory OPC-S.

Applications

  • For indoor, outdoor, duct, immersion temperature measurement for heating, ventilation and air conditioning applications.
  • Recording of minimum and maximum values for critical environments
  • Supervision of critical temperatures

Features

  • Precision temperature measurement for different ranges and accuracies
  • Minimum and maximum value memory
  • 0…10V, 0…20mA or 2…10V, 4…20mA measuring signals, selectable with jumpers
  • Optional alternative signal ranges programmable
  • Selectable averaging signal
  • Optional LCD display (OPC-S) or external display (OPA-S)
  • Status LED

Ordering

 Item name  Item code  Definition
 SCC-T1-Tp2  40-300075  Temperature transmitter without PT1000 sensing element. 
 Temperature range: -40…400°C (-40…752°F)
 SCC-T1-Tp2-OP  40-300076  Temperature transmitter as above with display.  
 Temperature range: -40…400°C (-40…752°F)

Accessories

#
Temperature Sensors
Passive temperature sensors for a large variety of installation options and applications
#
OPC-S - Built-in Display
Operation and display for intelligent duct and outdoor transmitters
#
OPA-S - Remote Display
Operation and display for intelligent transmitters

Downloads

Operation Manual

Install Sheet

Application Notes

Certificates

Archive